what is the safe distance to install an electric motor from a natural gas transmission line

Typical residential gas meter dimensions (C) InspectApedia.com Gas Meter Clearance Distance Q&A

  • POST a QUESTION or Comment about residential gas meter installation clearance distance codes & specifications

InspectAPedia tolerates no conflicts of interest. Nosotros have no relationship with advertisers, products, or services discussed at this website.


Gas meter clearance distance questions & answers:

Answers to common questions about the required distances between a gas meter and building walls, decks, fences, and other building features, openings, or appliances.

This article series provides a detailed table of case clearance altitude specifications for natural gas meter installations, giving the distances to various building features such equally windows, doors, electrical components, vents, air conditioners, and outside hose bibs.

Gas service line trench features are besides described.

Nosotros as well provide an ARTICLE INDEX for this topic, or you can try the page pinnacle or bottom SEARCH BOX as a quick way to find data you need.

Gas Meter or Gas Meter Regulator Vent Clearance Distance FAQs

These questions and answers virtually distances between a gas meter and other building or site features were posted originally at the topic home: GAS METER CLEARANCE DISTANCES - be certain to see the clearance spacing tables given at that place.

Photo: gas meters forth an alley in Tucson Arizona in the U.S. must exist protected from vehicle impact.

[Click to overstate any image]

I would be worried near that also, and I'd ask the local building or plumbing inspector and/or fire inspector to take a expect before that flame pit is used.

My neighbor is building an open flame fire pit less than 3 feet from gas meter. Also in that location is a line that runs from that gas meter secret to other meters in neighborhood which this fire pit is existence built over top of. Is this safe? If not, who practise I notify??

?

GAS METER CLEARANCE DISTANCES

has all of the common clearance distances yous'll observe in the model codes; yous won't notice "fire pit" in the gas codes but y'all volition find "sources of ignition" - typically 3 ft.

Just if it were my belongings I'd desire to exist much further away than that. After all, a fire pit not only makes a lot of heat, it can send off sparks. You want to be at least iii ft. (Opinion) from the greatest distance to which a fire pit spark or coal or ignition source might fly.

How far does a burn pit need to be from gas meter

WHAT SIZE GAS Pipe DO I Need FOR 100,000 BTU POOL HEATER IF IM 180 FEET Abroad FROM METER

Wes

Please encounter the distances given at the topic domicile page: GAS METER CLEARANCE DISTANCES https://inspectapedia.com/plumbing/Gas_Meter_Clearances.php

and let me know if that leaves you with any questions.

Tin can you lot install a water heater next to the gas meter if so what'southward the legal altitude it has to be away from the meter

Take a wait at all of the distances at

GAS METER CLEARANCE DISTANCES inspectapedia.com/plumbing/Gas_Meter_Clearances.php

and also consider that in improver to avoiding a potential ignition source (such equally a sparking electrical relay in the condenser/compressor unit), there are working space requirements for both the compressor-condenser unit and for the gas meter.

What distance should you keep an ac/heat pump away from gas meter in New York Land?

Take a look at all of the distances at

GAS METER CLEARANCE DISTANCES https://inspectapedia.com/plumbing/Gas_Meter_Clearances.php

where in that commodity - the home page for this topic - you'll find a table titled

Gas meter clearance to sources of ignition

cheers for asking

How far must my natural gas BBQ exist from the natural gas meter?

Len:

You will find clearances from buildings, obstructions and other site features at the home folio for this topic where we also discuss "working distance" around the sides and front of a gas meter.

GAS METER CLEARANCE DISTANCES inspectapedia.com/plumbing/Gas_Meter_Clearances.php

On that page in a table titled "Gas meter clearances to Landscape features, soil depths, soil encompass"

you'll find

Landscape features like shrubs or fences:

three feet articulate to front of meter

2 feet articulate to either side of meter

Please have a look.

How far from the side of my gas meter can I put my fence?
This is on Vancouver Island, Nanaimo B.C.

Thanks, Len

Great question, Calvin but sorry I can't answer with authority. Your gas visitor tin, nevertheless.

Sentinel out: moving the meter suggests that yous think that the extension of gas service pipage on the gas visitor side of the meter is going to be installed at their expense. That may non be the case.

My gas lines were all installed in the 1960s. The gas meter is at to the lowest degree forty feet away from my house. There is a leak somewhere between the meter and my business firm, presumably underground as the plumber has checked the exposed gas lines nether the house and only found three pocket-size leaks.

To dig up and supplant the 40 anxiety of line was estimated to exist about $1300. My question is, should the meter be closer to the house?

If so, shouldn't the gas company place information technology well-nigh the corner or side of the firm? And so the corporeality of line I'd demand to accept the plumber install would be significantly shorter, and cost significantly less.

Sach

Our home page for this topic GAS METER CLEARANCE DISTANCES

inspectapedia.com/plumbing/Gas_Meter_Clearances.php

Gives you working clearances

including from doorways, building corners, etc.

My gas meter is well-nigh the main entrance door. My question is how far the door from it should be?

Please accept a look and if that leaves y'all with any questions don't hesitate to enquire and we'll accept information technology from at that place.

My gas meter is near the master entrance door. My question is how far the door from it should be?

I saw the clearances effectually building structures, decks, etc. only i was wondering the distance around the meter in the state of VA. For case i will have a deck that will not sit high enough to cover the meter, so what is the clearance i need effectually information technology because i plan on having the deck built around it

. I was told when i called columbia gas VA that as long as they can service information technology and understand that if in that location is a leak that the deck will be ripped up to work on it. I am merely wondering the distance AROUND it non above or below. Thanks

Mary to be sure nosotros're talking well-nigh the same meter clearance distances delight run into the information at

GAS METER CLEARANCE DISTANCES

and let me know if you need more help.

I want to build an viii x 8 composite deck adjacent to my entry porch. The deck will be approximately iii.5 foot high. I will be able to step from my entry porch to it. I accept a gas meter on that side of the firm.

How much distance exercise I need from the pipe that leads from the meter read with elbow connection into the house. I live in a manufactured home so the pipe runs under the skirting to the other side of home.

Someone told me I need 3 feet from the side of that pipe and I don't quite go far. It would be attainable to a technician if it were to be repaired or replaced. Thanks.

Bob

I take non found any indication that there is a regular, calendar-based requirement for a gas visitor to supplant gas meters. The meter volition exist replaced if the company finds that it's damaged, obsolete, or unsafe: a status that may be discovered when the meter reader visits the site or when another official or a plumber or homeowner reports a gas meter concern.

If you have a business with the safety or condition of your gas meter you lot should contact your gas visitor immediately.

The Ohio Public Utilities Commission can exist contacted at
(800) 686-PUCO (7826)
(614) 466-3292 (in Columbus area)
7-1-one (TTY-TDD)

Fax
(614) 752-8351

Mailing Address
180 Eastward Broad Street
Columbus, Ohio 43215
Directions to the PUCO

Media Contact
Matt Schilling
(614) 466-7750

How often are gas companies required to supersede a gas meter in the state of Ohio?

You lot need to exist 3 feet away from the electrical box, Said. Your local plumbing inspector or gas company might, nonetheless, let you to extend the vent piping to that safety distance from the electrical equipment.

is there whatsoever gas meter vent that can exist install within 12 inch to the electric disconnect box

Me

In the table to a higher place giving gas meter clearance distances yous will see

"Gas meter clearance altitude to open up flame barbeque or cooker or to an incinerator or other open up flame device" = iii ft.

But Spotter OUT: "portable" means "movable" means that the clearance altitude could easily become dangerous. I'd besides worry about not just open flame but the possible effects of high heat on a gas meter or on nearby gas piping.

There may also be burn safety concerns nigh the altitude of the portable fire pit to nearby structures such as the trailers themselves. Ask your local edifice department of fire section for a burn down safety inspection.

How far from a gas meter is prophylactic to accept a portable fire pit? Neighbors have a burn pit going and there is a gas meter directly beyond from it. The burn is in between trailers that are approx. 15 feet apart in a trailer park

Gas meter clearance distances below balconies, entrance platforms, decks & porches

I'm edifice a deck and the gas meter is is against the house where the deck is running. What is the clearance needed to build the deck effectually it?

Jasin:

I don't consider the meter a hazard to ramp users provided guardrails protect it from any possible bear upon and provided you don't have a dope helping y'all who cuts a gas line while digging for the ramp back up posts.

To exist proper you lot should follow the clearances for gas meters given in a higher place at

Gas meter clearance distances below balconies, entrance platforms, decks & porches

I am worried that y'all may not exist giving adequate clearance around the meter front for hereafter maintenance or repairs, and more important, for safety there must be easy access to the gas line shutoff that 1 normally finds at the meter.

I accept an existing church with that would like to put a handicap ramp on the exterior of the edifice

. I accept an area of 7'-6" broad with a natural gas mater that volition be aside of the proposed ramp run. The width of the ramp is 3'-6" and the farthest part of the meter protrudes from the edifice 28".

The ramp will have a 34" loftier hand track (no guard required). This leaves 1'-8" from the front of the meter to the edge of the ramp/handrail. What would the minimum clearance in front of the meter demand to be?

Jasin:

I don't consider the meter a gamble to ramp users provided guardrails protect information technology from any possible impact and provided you don't have a dope helping you who cuts a gas line while digging for the ramp support posts.

To be proper yous should follow the clearances for gas meters given higher up at

Gas meter clearance distances below balconies, entrance platforms, decks & porches

I am worried that you may not be giving adequate clearance around the meter forepart for futurity maintenance or repairs, and more important, for prophylactic there must exist easy admission to the gas line shutoff that one usually finds at the meter.

I have an existing church building with that would like to put a handicap ramp on the exterior of the building.

I have an area of 7'-6" wide with a natural gas mater that will be aside of the proposed ramp run.

The width of the ramp is 3'-6" and the farthest part of the meter protrudes from the building 28".

The ramp will take a 34" loftier paw rail (no baby-sit required). This leaves 1'-8" from the front of the meter to the edge of the ramp/handrail. What would the minimum clearance in front of the meter need to exist?

Eric

The final answer is going to exist from your building and zoning departments.

But certainly besides giving a ten foot or more clearance for future work/excavation/repairs, y'all demand to be very sure that excavation or work for constructing the foundation of your garage doesn't cut into, affect, or build likewise close to or over a buried gas line without first building section blessing.

Hitting a gas line while earthworks for a ground for your garage could be a once in a lifetime, final experience.

when putting a garage right next to another building how far abroad exercise i have to put the garage. the gas meter is right in between the existing building and the new garage. how far practise i have to put the new garage from the gas meter

Harold your message left me confused - lost some words. But if you aroma gas there is risk of an explosion or fire.

You should telephone call your gas company - from some other, safe location. Do Not flip light switches, use a telephone, make sparks, etc. anywhere that you smell gas and keep people away until you know the building is safe.

They moved our gas meter and put it right against our house and we can smellgas coming from the meter is this legal to put it so close

Re-posting

Writer:jerry (no email)

Annotate:Q: Are tenants in a multi-family residence required to accept unrestricted access to their gas and/or electric meters which are located in a utility room with all the meters for the building?

The NEC code sections 110.26 and 240.24 discuss admission to the electrical utility room, but exercise not appear to require unsupervised tenant access

. In fact 110.26 describes access by qualified persons to equipment behind a locked door is adequate. In the case of this building simply the gas meters are in the utility room; electric meters are located on the outside rear of the structure and are accessible to tenants without restriction.

It is my opinion that admission to an otherwise lawmaking-compliant utility room may be via a locked door accessible on reasonable discover to a designated person

--- manager, Management Visitor, building supervisor or possessor-- for access to inspect the gas meters. I have not found a requirement that directly tenant admission to the front of that locked door via a dedicated stairway is required.

thy install a new meter last week and raised ti two feet of the ground and it looks like honey abreast my house

Rather than an absolute limit, more than likely y'all'll have to go to a larger diameter pipe and possibly to a staged regulator system. Check gas pipage tables in the UPC or with your edifice department.

What is the furthest altitude I can run a gas line?

I call up and so, Tyler, simply the proper authority, the only i in fact who has final word is your local building lawmaking or edifice plumbing inspector. Let me know what she or he says.

The worry is probably mostly 1 of access space or arcing motor hazards

My plumber installed a sump pump and ran the 2" line out my rim about 12" abroad from the gas meter. If this is cached and sealed, volition I be in compliance?

How much distance is required for a driveway next to a gas meter?

I am the director of a mobile home park in northern Alberta Canada. my question is how far from the existing natural gas line/meter can a mobile home exist placed. The service line is appox six feet out the end of the mobile secured to a debate line. This places the service approx. 2 to 2 1/2 anxiety from the meter claw upwardly.

What is the clearance between the gas meter and vent on a high efficiency furnace

Interesting question, Most likely he'south entirely correct, and is using the same AGA sources you see in the article above - have a look at the table and yous'll meet crawl infinite vents are included along with clearance distances.

The gas meter was installed straight in front of a crawl space foundation vent. The vent was at that place when the gas line and meter was installed. A home inspector now says that the vent has to be covered and sealed. Is he correct?

Can I employ my charcoal/wood smoker on the aforementioned side of the house where my gas meter is? Information technology would exist about 15-xx feet abroad.

Jason this is a question to take to your gas supply company.
Problems I tin forsee include:

1. some idiot driving a fencepost through a utility line causing a ending

2. making it impossible to visually read the meter. Some systems use a transponder and meters are read remotely, requiring only occasional directly visual admission.

Allow me know what your gas company says. Meanwhile don't move the argue nor drive posts nor dig into ground before you also know what utilities such equally cached gas lines demand to be avoided, and where they are located.

Tin can I motion my fence to where the gas meter would exist behind the the contend. I live in Wichita Falls Tx.

Currently the argue is behind the meter where information technology had open access for its meter readings. I was wanting to build a new fence and not take to remove it due to the gas company non exist able to read the meter or violate some code.

The customer service line is not open for til Monday. I was trying to get it done today while I'one thousand off. Thanks

Cecelia,

You don't say where y'all live, so we cannot even guess at what codes use to you regarding gas meters and gas pipage. In any instance usually allow questions are usually a local edifice code matter.

You lot need to call your local gas company OR your local building department to enquire their advice likewise as ask a recommendation for who can handle this chore as making a mistake could exist dangerous.

If the meter belongs to the park, it's not clear to me that a park tenant should or even legally could motion their meter.

I sold my mothers Mobile Home, gas meter is as you go into her door simply below it. Park owner says I demand to have it moved abroad from the front. It's not PG&E meter it's the parks meter. Do I demand a permit to motion it. Park manager is a very mean person.

The city inspector left me a correction discover stating that the gas regulator I installed needed to be 3' in a higher place the fresh air intake from the HVAC system or 10' away, is this right? on this web site it indicates 10' either manner.

Darren,

In that location are clearance distances between a gas meter and flame sources or other hazards, so I'm nervous about what you describe. (Meet the tables above).

Some building officials will "grandfather" an indoor gas meter provided that its regulator vent is piped to the outdoors. Let me know what your building department says.

We are renewing kitchen units. The gas meter is in a kitchen unit of measurement which is straight next to the cooker point. Is this allowed?

In that location is no relationship between gas meters and radon mitigation or testing systems other than giving standard gas meter clearances for access and maintenance.

How far does a radon organisation coming out of a home demand to exist from a gas meter in the city of ST Paul MN

John, the gas meter clearances in this commodity series are typically from finished wall surfaces. Add 1-two" to your framing to allow for finished materials.

How close tin interior framing be to a gas meter?

how far does the electrical meter have to exist from the gas meter

Quoting the NYC Fuel Gas Code Appendix East every bit an case that has some helpful language:

3. Gas meter rooms, when provided, shall at all times be kept clear of all rubbish; and shall not exist used in whatever mode for storage purposes, including material or equipment of whatever kind.

A legible sign reading "Gas meter room—

No storage permitted" shall be permanently and conspicuously posted on the outside of the meter room door, except that the sign may be posted on the interior of the meter room door in Occupancy Group R-3.

The lettering of such signs shall be of assuming type at to the lowest degree 1 inch (25 mm) in pinnacle and shall exist properly spaced to provide good legibility. The lettering and groundwork shall be of con- trasting colors.

Where gas meters and related equipment are not located in a separate room simply are located in an open floor expanse, no flammable fabric shall be stored or kept within 5 feet (1524 mm) of such equipment; nor shall the gas meter exist within three anxiety (914 mm) of any heating boiler or sources of ignition and, except Occupancy Group R-3, there shall exist a concrete bulwark required if the room is also used for storage purposes or the like.

how close should a gas meter be to rubbish and stdorage

...


Go along reading at GAS METER CLEARANCE DISTANCES or select a topic from the closely-related articles beneath, or see the consummate Article INDEX.

Or see GAS METER CLEARANCE Distance FAQs-two - more than-contempo questions and answers almost clearance spacing distances around gas meters

If your fuel supply is from onsite LP gas storage rather than piped-in natural gas fed through a meter then you should refer to GAS TANKS, LP for LP gas tank clearance distances and installation specifications.

Besides see GAS FIREPLACE VENT CLEARANCE REQUIREMENTS

GAS PIPING CLEARANCES, CODES & DEFECTS

Or see these

Gas Meter Manufactures

  • GAS LP & NATURAL GAS Condom HAZARDS
  • GAS BTUH, CUBIC FEET & Energy - how to calculate or catechumen between cubic feet of gas, liquid gallons of LP gas, and BTUs per cubic foot or gallon of gas fuels.
  • GAS LEAK DETECTION, LP / NG
  • GAS METERS
    • GAS METER CLEARANCE DISTANCES
    • GAS METER CODES & STANDARDS
    • GAS METER PROTECTION BOLLARDS
  • GAS Pipe, VALVES, CONTROLS - home
  • LP / PROPANE GAS TANKS

Suggested commendation for this spider web page

GAS METER CLEARANCE Distance FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: Article INDEX to GAS APPLIANCES, PIPING, CONTROLS

Or utilise the SEARCH BOX institute below to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Questions & answers or comments about residential gas meters, inspection, diagnosis, repair.

Endeavour the search box just below, or if you lot adopt, post a question or annotate in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an paradigm, spider web link, or text that looks to the software every bit if it might be a web link, your posting volition appear after it has been approved by a moderator. Apologies for the filibuster.

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman